Specifications - ADM and MCM
ADM (Air Distribution Module) Factory assembled air duct and powered-fan module set to fix underneath Air-Diffusion panel. Aluminum grille lays on the Air-diffusion panel, flange on top of floorcovering.
|
|
Grille
|
|
|
Anodized aluminum frame with grille, bottom 4 mm thick form strip connect to air duct, to prevent air leakage. Size: 416 mm x 145 mm x 47 mm Grill gauge: 4.5 mm, perforate ratio 24% Loading property: greater than 500 kg
|
|
aluminum grille
|
|
|
Air duct Dimension: 362 mm x 160 mm x 175 mm (H) galvanized steel, welded form, bottom opening to connect and receive supply air from powered-fan, upper opening to receive aluminum grilles. 3 mm recession at base of the duct to stop dirt or objectives dropping through openings at the grille.
Powered fan Dimension: 400 (L) x 230 (W) x 200 (H) 4-line contact Control Board Input: AC 220V Frequency: 50Hz Power Consumption: 35W (Max) Operation Humidity: 57°C / 90% (Max)
|
|
ADM assembly: air-duct as interface of powered-fan and grille. Grille lays on top, flanges set on floor covering.
|
|
|
|
|
|
|
Hi
|
1350 +/- 50
|
200 +/- 5%
|
50 +/- 2
|
Standard
|
1150 +/- 50
|
150 +/- 5%
|
45 +/- 2
|
Lo
|
900 +/- 50
|
100 +/- 5%
|
40 +/- 2
|
|
|
Air-diffusion panel Full steel factory fabricated Air-diffusion panel size 600 mm x 600 mm with opening 372 mm (W) x 115 mm (D) at side to accommodate air duct and grille. Top of powered-fan is designed to bolt and lock underneath the panel. Shock absorption rubber pad in-between the air diffusion panel and the powered-fan. The air diffusion panel lays on stringers and interchangeable with any other access floor panel.
Access floor system Access panel size: 600 mm x 600 mm Finish floor height (FFH): 300 mm ~ 400 mm, minimum FFH shall be 250 mm, to have floor void no less than 210 mm clearance. Loading property: concentration load shall be greater than 450 kg (1,000 LB). Flammability: Non-combustible. Access floor panel shall be made of full steel, steel cementitilous, calcium sulphate, or other non-combustible materials. Understructure: Bolted stringer as specified by the access floor manufacturer. Cables and floor trunkings: plan and spread at flat height no more than 120 mm high.
|
|
|
|
|
Copyright Netfloor, Inc. All Rights